Description
Description
Model | C500D5P |
Duty | Prime |
Power Rating (kVA / kWe) | 500/400 |
No. of Phases | 3 |
Output Voltage and Frequency (V and Hz) | 415 V, 50 Hz |
Power Factor | 0.8 (lagging) |
Current (A) | 695 |
RPM | 1500 |
Engine Specification | |
Make | Cummins® |
Model | KTAA19-G10 |
MoEF Certified Power (hp) | 587 |
Required Power for Rated kVA (hp) | 587 |
Cooling | Liquid Cooled (EG Compleat 50:50) |
Aspiration | Turbocharged, Charge air Cooled |
No. of cylinders | 6, In-line |
Bore(mm) x Stroke(mm) | 159 x 159 |
Compression ratio | 16.7:1 |
Displacement(litre) | 19 |
Fuel | High Speed Diesel |
Fuel consumption @75% load with radiator and fan* (litre/hr) | 79.83 |
Fuel consumption @100% load with radiator and fan* (litre/hr) | 103.64 |
Performance class of genset | ISO 8528-5 G2 |
Starting system | 24 V DC Electrical |
Lube oil specification | CH4 15W40 |
Lube oil sump capacity, High-Low level (litre) | 38-32 |
Total lubrication system capacity (litre) | 50 |
Total coolant capacity (litre) | 85 |
Exhaust pipe size (inch) | 10 |
Total wet weight (Engine+Radiator) (Kg)## | 2300 |
Length x Width x Height (Engine) (mm) | 1744 x 916 x 1402 |
Mean piston speed (m/s) | 7.95 |
Combustion air intake @100% load (±5%) (cfm) | 1278 |
Exhaust Temperature (°C) | 464 |
Alternator specification | |
Make | Stamford (CGT) |
Alternator frame | HCI544D |
Enclosure | IP 23 |
Voltage regulation (Max.) | ±1% |
Class of Insulation | H Class |
Winding Pitch | 2/3 |
Stator Winding | Double layer lap |
Rotor | Dynamically Balanced |
Waveform distortion/ Total Harmonic Distortion | No load < 1.5 %, Non-distorting balanced linear load < 5 % |
Maximum Unbalanced Load across phases# | less than or equal to 25% |
Telephonic Harmonic factor | < 2% |
Genset Model | C500D5P |
Rating (kVA) | 500 |
Length (mm) | 6000 |
Width (mm) | 2000 |
Height (mm) | 2250 |
Wet Weight## (kg) | 7600 |
Standard Fuel tank Capacity (litre) | 690 |
Shipping Information
Shipping Information
Please contact: +971 527224450 to get delivery information