Description
Description
Model | C100D5 | C125D5P |
Duty | Prime | Prime |
Power Rating kVA/kWe | 100/80 | 125/100 |
No. of Phases | 3 Phase | 3 Phase |
Output Voltage and Frequency (V and Hz) | 415 V. 50 Hz | 415 V. 50 Hz |
Power Factor | 0.8 (lagging) | 0.8 (lagging) |
Current (A) | 139 | 174 |
RPM Engine Specification | 1500 | 1500 |
Make | Cummins® | Cummins® |
Model | 6BTAA5.9-G13 | 6BTAA5.9-G13 |
MoEF Certified Power (hp) | 159 | 159 |
Required Power for Rated KVA (hp) | 129 | 158 |
Cooling | Liquid Cooled (EG Compleat 50:50) | Liquid Cooled (EG Compleat 50:50) |
Aspiration | Turbocharged Charge Air Cooled | Turbocharged Charge Air Cooled |
No. of cylinders | 6, In-line | 6. In-line |
Bore (mm) x Stroke (mm) | 102 x 120 | 102 x 120 |
Compression ratio | 16.5:1 | 16.5:1 |
Displacement (litre) | 5.9 | 5.9 |
Fuel | High Speed Diesel | High Speed Diesel |
Fuel consumption @75% load with radiator and fan* (itre/hr) | 18.32 | 22.5 |
Fuel consumption @100% load with radiator and fan* (ltre/hr) | 24.60 | 30.25 |
Performance class of generator set | ISO 8528-5 G2 | ISO 8528-5 G2 |
Starting system | 12 V DC Electrical | 12 V DC Electrical |
Lube oil specification | C14+ 15W40 | C14+ 15W40 |
Lube oil sump capacity, High-Low level (litre) | 19.9-14.9 | 19.9-14.9 |
Total lubrication system capacity (litre) | 21.4 | 21.4 |
Total coolant capacity (litre) | 26 | 26 |
Exhaust pipe size (inch) | 4 | 4 |
Total wet weight (Engine+Radiator)* (kg) | 523 | 523 |
Length x Width x Height (Engine) (mm) | 1066 x 725 x 1033 | 1066 x 725 x 1033 |
Mean Piston speed (m/s) | 6 | 6 |
Combustion air intake @100% load (+5%) (cfm) | 311 | 311 |
Exhaust Temperature (C) Alternator Specification | 553 | 553 |
Make | Stamford (CGT) | Stamford (CGT) |
Alternator Frame | UCI274C | UC1274V |
Enclosure | IP 23 | IP 23 |
Voltage regulation (Max.) | ±1% | ±1% |
Class of Insulation | H Class | H Class |
Winding Pitch | 2/3 | 2/3 |
Stator Winding | Double layer lap | Double layer lap |
Rotor | Dynamically Balanced | Dynamically Balanced |
Waveform distortion/Total Harmonic Distortion | No load < 1.5% Non distorting balanced linear load < 5% | No load < 1.5% Non distorting balanced linear load < 5% |
Maximum Unbalanced Load across phases | less than or equal to 25% | less than or equal to 25% |
Telephonic Harmonic factor | < 2% | < 2% |
Genset Model | C100D5P | C125D5P |
Rating (kVA) | 100 | 125 |
Length (mm) | 4000 | 4000 |
Width (mm) | 1150 | 1150 |
Height (mm) | 1850 | 1850 |
Wet Weight** (kg) | 2200 | 2200 |
Standard Fuel tank Capacity (litre) | 290 | 290 |
Shipping Information
Shipping Information
Please contact: +971 527224450 to get delivery information